What does this calculator do?
The power factor tells you what fraction of the apparent power is turned into useful active power.
PF = P / S
Enter the values in the units shown. The calculator converts units automatically and displays the result in practical units.
Worked example
P = 900 W and S = 1000 VA give PF = 0.9.
Practical tips
- A valid result lies between 0 and 1.
- A low value means more current for the same useful power.
- For real correction, distinguish inductive from capacitive loads.
Common mistake to avoid
A value close to 1 does not guarantee low harmonic distortion; this simplified calculation assumes sinusoidal conditions.
Complete power factor formulas
In AC circuits there are three powers, which form the power triangle: active power P (W), which does work or produces heat; reactive power Q (var), which is exchanged with magnetic or electric fields; and apparent power S (VA), which is what the network “sees”: S = V · I.
- Power factor: PF = P / S
- With sine waves: PF = cos φ, where φ is the phase angle between voltage and current
- Apparent power: S = √(P² + Q²)
- Reactive power: Q = √(S² − P²) = S · sin φ
- Angle: φ = arccos(PF)
- Current required: I = P / (V · PF) in single-phase
- Capacitor correction: Qc = P · (tan φ1 − tan φ2) and C = Qc / (2π · f · V²)
With non-linear electronic loads (switch-mode supplies without PFC, variable-speed drives), the current contains harmonics: PF = P / S is still valid, but it no longer equals cos φ.
Typical values (S = 1000 VA)
| PF | Angle φ | P | Q | Relative current |
|---|---|---|---|---|
| 1.00 | 0° | 1000 W | 0 var | 1.00 × |
| 0.95 | 18.19° | 950 W | 312 var | 1.05 × |
| 0.90 | 25.84° | 900 W | 436 var | 1.11 × |
| 0.85 | 31.79° | 850 W | 527 var | 1.18 × |
| 0.80 | 36.87° | 800 W | 600 var | 1.25 × |
| 0.70 | 45.57° | 700 W | 714 var | 1.43 × |
| 0.50 | 60.00° | 500 W | 866 var | 2.00 × |
The last column shows how much more current you need to deliver the same active power as with PF = 1 (it is 1 / PF). At PF = 0.5 the conductors carry twice the current.
Worked example: correcting a motor’s power factor
A single-phase motor draws 1500 W at 230 V, 50 Hz, with PF = 0.75. The goal is 0.95.
- Initial current: I = 1500 / (230 × 0.75) ≈ 8.70 A.
- tan φ1 = tan(arccos 0.75) ≈ 0.882 and tan φ2 = tan(arccos 0.95) ≈ 0.329.
- Reactive power to compensate: Qc = 1500 × (0.882 − 0.329) ≈ 830 var.
- Capacitance: C = 830 / (2π × 50 × 230²) ≈ 50 µF (use the nearest standard AC-rated capacitor with a suitable voltage rating).
- Final current: I = 1500 / (230 × 0.95) ≈ 6.86 A, about 21 % less.
The active power does not change: the motor does the same work, but the installation carries less current and has lower losses.
Common mistakes
- Confusing power factor with efficiency: efficiency compares mechanical and electrical power; PF compares active and apparent power. A motor can be efficient and still have a low PF.
- Entering P greater than S: that is physically impossible; check your measurements or units (kW versus VA).
- Overcompensating: too much capacitance makes the load capacitive and the PF drops again, now leading.
- Correcting harmonic-rich loads with plain capacitors: they can resonate with the grid; such loads need detuned filters or active correction.
Frequently asked questions
What is a good power factor?
Industrial installations usually aim for 0.9–0.95 or higher. Many utilities charge for reactive energy when a customer’s PF falls below the limit set in their tariff; check the terms of your supply.
What do lagging and leading power factor mean?
Lagging (inductive) means the current lags the voltage, as in motors and transformers. Leading (capacitive) means the current leads, as with capacitor banks or long unloaded cables.
How do I calculate active power if I know V, I and PF?
P = V · I · PF in single-phase, with the AC power calculator, or P = √3 · VL · IL · PF in three-phase, with the three-phase power calculator.